Nca 2 Notifier Manual

Posted on

NCA-2 Manual — P/N 52482:M1. Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability. FieldServer FS-8700-130 Notifier NCA2-NFS2-3030 Driver Manual (Supplement to the FieldServer Instruction Manual) APPLICABILITY & EFFECTIVITY. Nca-2, Onyx, Series network control annunciator • Read online or download PDF • Notifier NCA-2 User Manual.

The NOTIFIER NCA-2 is a second-generation Network Control Annunciator for the NOTI-FIRE-NET or High Speed NOTI-FIRE-NET networks, compatible for use with ONYX® Series nodes such as the NFS2-3030, NFS-3030, NFS-320, NFS-640 and NFS2- 640 fire alarm control panels, as well as first-generation NCA Network Control Annunciators. Additionally, the NCA-2 may be configured with DVC Series products to create one or more Digital Audio Command Centers on NOTI-FIRE-NET or High Speed NOTI-FIRE-NET. The NCA-2 provides system control and display capabilities for all, or for selected network nodes. Features & Benefits:.

Nca 2 Notifier Manual

Network-wide: Acknowledge, Silence, Reset. Individual Enable/Disable or Group Enable/Disable local and networked NFS2-640/NFS2-3030/NFS-320 points and zones. Full supervision of all inputs and network integrity.

Enhanced-format 640-character LCD display with backlighting. Alphanumeric QWERTY rubber keypad with tactile and audible feedback. Network History Buffer. Multiple passwords and access levels. Full network monitoring of all nodes. Full command and control over entire network.

Supports Digital Voice Command (DVC) for network audio applications. Inherently regenerative system. Each node acts as a repeater to reshape and regenerate data signals Compatibility:.

NOTI-FIRE-NET Networks. High Speed NOTI-FIRE-NET Networks. NFS-3030/NFS2-3030. NFS-640/NFS2-640. NFS-320. AM2020/AFP-1010. AFP-200/300/400 Listings:.

UL Listed: file S635. ULC Listed: S635. FM approved. CSFM: 7165-0028:0224, 7165-0028:0243. MEA: 232-06-E.

FDNY: COA#6114, COA#6121. Biology brooker 2nd edition study guide.

Nca 2 Notifier Manual

DN-7047:F. — Page 3 of 4 HS-NCM-W/MF/SF/WMF/WSF/MFSF: High-speed network communications modules. Wire, single-mode fiber, multi- mode fiber, and media conversion models are available.

See DN-60454 ABS-2D: Annunciator Backbox, Surface, black. Mounts one NCA-2 and one NCM-W/-F. ABS-2DR: Same as above, but red. CHS-2D: Chassis, required whenever the NCA-2 is mounted in an ABS-2D(R). CHS-M3: Chassis, mounts an NCA-2 in a single row of a CAB-4 Series cabinet.

CA-2: Chassis, Audio, 2 rows. Mounts an NCA-2 and the DVC Digital Voice Command in two rows of a CAB-4 Series cabinet. CAB-4 Series Enclosure: Available in four sizes, “A” through “D”. Backbox and door ordered separately; requires BP2-4 battery plate. CAB-BM Marine System: Protects equipment in shipboard and waterfront applications.

Nca 2 Notifier Manual Fire

Order NCA-2-M; for non-English order NCA-2-M and the appropriate KP-KIT-XX. (See DN- 60688.) Also order BB-MB for systems using 100 AH batter- ies. For a full list of required and optional equipment, see DN- 60688. DP-DISP: Annunciator Dress Plate.

Dress plate is used when NCA-2 is mounted in the top row of a CAB-4 Series cabinet with a CHS-M3 chassis. NCA-2RETRO: Kit for retrofit mounting the NCA-2 to a DP- DISP dress plate. NCA/640-2-KIT: Mounting kit for directly mounting the NCA-2 to CPU2-640 chassis. LCD-160: 160 character LCD annunciator. See DN-66940 LCD2-80: 80 character LCD annunciator.

See DN-60548 TR-ABS2D: Trim ring for semi-flush mounting of ABS-2D. Agency Listings and Approvals These listings and approvals apply to the NCA-2. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Con- sult factory for latest listing status. UL Listed: file S635.

ULC Listed: S635. FM approved. CSFM: 7165-0028:0224, 7165-0028:0243. MEA: 232-06-E. FDNY: COA#6114, COA#6121. Marine Applications: Marine approved systems must be con- figured using components itemized in the Marine ONYX Sys- tems datasheet DN-60688. Specific connections and requirements for those components are described in the Marine- EQ installation document, PN 54756.

When these requirements are followed, systems are approved by the following agencies:. US Coast Guard 161.002/55/0 (Standard 46 CFR and 161.002). Lloyd's Register 11/600013 (ENV 3 category). American Bureau of Shipping (ABS) Type Approval.

NOTE: For information on the CAB-BM marine system, see DN-60688.